MG Series - Class 2 Outlet Transformers
|
Description: These transformers are used for metal outlet box and security products. It could be an open frame transformer or a power supply which is sealed by plastic enclosure. As an open frame type, it is provided with UL lead wires for input and 2 screws for output connection. As a power supply, it is provided with an AC voltage with maximum output rating of 50VA. They can provide a mounting tab on the top of case, screws for output connection. Grounding is also available.
|
|
|
Features:
High efficiency, low heat generation
Full approvals & UL
100,000 hours MTBF
Over heat protection or Class 2 inherently limit
Graceful appearance
|
|
Electrical Characteristics
| Input Voltage & Frequency |
UL/CSA
|
120VAC 60 Hz
|
| Rated Input Power |
(Shown on the label) |
|
| Exciting Current |
Depends on requirement or design |
150 mA Max. |
Output Rating
Voltage
Current / VA
|
Full Load
Various (see tables) +/- 5%
Various (see tables) 50VA Max.
|
No Load
125% output voltage Max.
0 mA
|
| Insulation Resistance |
|
500VDC 100MΩ MIN. |
| Dielectric Strength |
Input - Output (UL/CSA version)
|
1.24KV for 1 minute
|
| Operating Environment
|
Temperature
Humidity
|
-10ºC ~ 40ºC
20% - 80%
|
| Storage Environment |
Temperature
Humidity
|
-20ºC ~ 70ºC
20% - 90%
|
| Insulation Grade |
CLASS A, E, B |
Min 105ºC. Max 130ºC |
| Temperature Rise |
|
75 Deg. Max. @ rated load |
| Agency Safety |
Power supply: UL-1310, CSA 22.2 No.223
Power transformer: UL-1585
|
| Efficiency |
70% Normally @ rated load |
| Protection |
Built a 115ºC or 130ºC thermal fuse on the primary winding.
Inherently limited protection or non-inherently limited (fused secondary) |
Mechanical Description:
| Core Size |
From EI-41, 48, to EI-57 |
| Enclosure Type |
Power transformer (with Channel frame and end bell, provide mouting leg)
Input: 2 lead wires or 3 lead wires(grounding option) with screw bolt.
Output: 2 screws
Power supply (plastic enclosure with mounting tab)
Input: AC blades with grounding pin or not.
Output: 2 screws or 3 screws (grounding function)
|
|
|